JAKI ENTERPRISE CO., LTD.
886-4-24915501
886-4-24954240
No.11, Lane 2, Rencih St., Dali City, Taichung County 41282, Taiwan
www.jaki.com.tw

Products

Soft Starters.
Three Phase - Soft Start of OL Series
SMC9XXXXX-OL

1. Soft start time and start torque can be adjusted, let soft starter smooth.

2. 3 starting ways can be choice in this machine: slope starter, current-limit starter, current-limit and kick starter.?

3. Use the S.C.R. control: No contacts, no arc, no wear and tear, the equivalent of semipermanent life.

4. Wiring easy: installation of 3 in 3 out, save the coast of hand wiring.

5. This controller is microprocessor with the function of automatic light/heavy loading revision and torque control.

6. Cooling fans has temperature control, the cooling sheet working at 55C, and stop at 45C, this design can extend use-life of fans 2-3 times.

7.The controller inside electronic sensor of CT: overload protection, input power loss the phase protection, motor block protection, controller over temperature protection, exceed sensitive reaction and no thermal effect, not affected by ambient temperature.

8. The machine has 3 sets output connection points: The output point when starting (Running), after running the output contacts (by Pass), and output point for system abnormal (NO, COM NC).

Safety/Quality Approvals

CE, IEC60947-4-2 certified the specification.

Compact Series.
SMC920020-OL, SMC920030-OL, SMC920050-OL, SMC920075-OL, SMC920100-OLSMC930020-OL, SMC930030-OL, SMC930050-OL, SMC930075-OL, SMC930100-OL, SMC930150-OL

Specification

  • Main power: AC 208/220/380/440/480 VAC 10%
  • Auxiliary voltage: AC 220V±15% 50/60Hz
  • Start way: dry contact point
  • Rated current: 4A~28A
  • Horse power: 2HP~15HP
  • Work frequency: 50~60Hz ±5%
  • Highest peak pressure proof: 600V or 1200V~1600V
  • Soft start time: 1~40 sec.Start torque: 100%~500%
  • Environment: -10°C~50°C Humidity Under 90% RH.
  • Insulation resistance: Over 20 MΩ (power & external cover) Over 20 MΩ (input signal & external cover).
  • Strength of press-resisted: 2500VAC/1min between power & external cover 1000VAC/1min between power & external cover.

Feature

Soft-start motor controller, use the blowing machine's motor, mixing machinery, milling machinery, smash machinery, overhead cranes, oil pressure elevator, soft start, reducing the instantaneous starting current. When the motor abnormality, can protect the motor.

 

Mold
Machine
Vehicle
Contact Supplier
Browsing History
Scroll Up
EZB2B.TW uses cookies,IP to collect data and continually improve the website. By continuing to use this website, you must agree to the use of cookies and IP.